Please use this identifier to cite or link to this item: https://hdl.handle.net/11147/9045
Title: Reactive power capability model of wind power plant using aggregated wind power collection system
Authors: Sarkar, Moumita
Altın, Müfit
Sorensen, Poul E.
Hansen, Anca D.
Keywords: Reactive power capability
Wind power plant
Wind power collection system
Aggregated
Wind integration studies
Long term voltage stability
Publisher: MDPI Multidisciplinary Digital Publishing Institute
Abstract: This article presents the development of a reactive power capability model for a wind power plant (WPP) based on an aggregated wind power collection system. The voltage and active power dependent reactive power capability are thus calculated by using aggregated WPP collection system parameters and considering losses in the WPP collection system. The strength of this proposed reactive power capability model is that it not only requires less parameters and substantially less computational time compared to typical detailed models of WPPs, but it also provides an accurate estimation of the available reactive power. The proposed model is based on a set of analytical equations which represent converter voltage and current limitations. Aggregated impedance and susceptance of the WPP collection system are also included in the analytical equations, thereby incorporating losses in the collection system in the WPP reactive power capability calculation. The proposed WPP reactive power capability model is compared to available methodologies from literature and for different WPP topologies, namely, Horns Rev 2 WPP and Burbo Bank WPP. Performance of the proposed model is assessed and discussed by means of simulations of various case studies demonstrating that the error between the calculated reactive power using the proposed model and the detailed model is below 4% as compared to an 11% error in the available method from literature. The efficacy of the proposed method is further exemplified through an application of the proposed method in power system integration studies. The article provides new insights and better understanding of the WPPs' limits to deliver reactive power support that can be used for power system stability assessment, particularly long-term voltage stability.
Description: Sarkar, Moumita/0000-0003-0706-2370; Hansen, Anca Daniela/0000-0002-2092-8821; Sorensen, Poul/0000-0001-5612-6284; Altin, Mufit/0000-0002-3650-3131
URI: https://doi.org/10.3390/en12091607
https://hdl.handle.net/11147/9045
ISSN: 1996-1073
1996-1073
Appears in Collections:Energy Systems Engineering / Enerji Sistemleri Mühendisliği
Scopus İndeksli Yayınlar Koleksiyonu / Scopus Indexed Publications Collection
WoS İndeksli Yayınlar Koleksiyonu / WoS Indexed Publications Collection

Files in This Item:
File Description SizeFormat 
energies-12-01607.pdfMakale (Article)1.6 MBAdobe PDFThumbnail
View/Open
Show full item record



CORE Recommender

SCOPUSTM   
Citations

21
checked on Nov 15, 2024

WEB OF SCIENCETM
Citations

15
checked on Nov 9, 2024

Page view(s)

5,390
checked on Nov 18, 2024

Download(s)

886
checked on Nov 18, 2024

Google ScholarTM

Check




Altmetric


Items in GCRIS Repository are protected by copyright, with all rights reserved, unless otherwise indicated.